RE: Is there a Power Pro that can say yeah or nay before I do this..

A 3-wire 220V circuit (like the hot tub or AC) has two hots and a ground (no neutral). You CAN NOT use the ground as a neutral. The only options her...

9 years ago
Topic
Replies: 3
Views: 8
Reply
RE: Learning DMX pcb construction

You are trying to do many things at once, all of which need to work in order to get a result, and if something doesn't work, you don't know enough to ...

9 years ago
Reply
RE: Wire gauge needed for 24amp load per bank

Voltage is not an issue when choosing wire gauge. Voltage drop is. Wire has resistance. Google "wire resistance per foot". The amount of voltage d...

9 years ago
Forum
Reply
RE: flood lights fail

I don't believe that board allows using an LED with a common cathode. Try removing the tab that connects the three pins together on that side of the ...

9 years ago
Reply
RE: What Do You Do For A Living?

Hardware and software engineer for a major lighting company, doing embedded controls.

9 years ago
Forum
Reply
RE: Serial to RS485 Transciever

A few notes: - The 7805 outputs 5V, not 5.5V so it should be called VCC_5V_REG. I would call the supply to U2 VCC_U2. I would also add a note to th...

10 years ago
Forum
Reply
RE: Radio Shack

The parts drawers are down to 90% off. I just filled two bags of bits... /mike

10 years ago
Topic
Replies: 2
Views: 9
Reply
RE: Controller mounted to Wood?

Cut down Bic pens (with the ink removed 🙂 make good cheap spacers as well. /mike

10 years ago
Forum
Reply
RE: Power Cords

Check the gauge on the computer power cords. 14AWG is good for 15A, 16AWG for 13A, and 18AWG for 10A max. PC power cords come in all of the above. ...

10 years ago
Reply
RE: Getting power from the house

As a side note - I see at least one 30A fuse in there - make sure that the wiring on that circuit really is 10AWG; if it isn't, change the fuse back t...

10 years ago
Reply
RE: This is why we fuse everything.....

Looks like a simple thermal circuit breaker. They are not polarity sensitive.

11 years ago
Reply
RE: Project LED house outline

Looks like a Behringer Xenix 302USB

11 years ago
Forum
Reply
RE: DMX Fire / Flame Machine Fuel To Use?

Do those have provisions for a dead-man switch? DMX isn't safe or approved as a control mechanism for pyro or automation by itself (there's no error ...

11 years ago