Your saying to avoid using a 3 core wire that has data and ppwer running through the same cable?
It was a 3 core cable with power data and ground. I had some 20/4 shielded in the garage. I Tied two conductors together, effectively making it 17 gau...
So i have a little hiccup with my project. I got some of the install done on 3 sides of the house. 590 pixels so far. On one side i have 212 pixels th...
Gotcha. Thank you.
Can you use a low voltage landscape lighting wire such as this? Would that be suitable for power injection?
One more question (I swear im almost done!) The dormer is quite a distance from the controller. Probably 100 plus ft. I was planning to run that on i...
So in my scenario what would you do? If i install a 2nd ps in the front corner, im still going to have an injection point that is 50 ft or so away. A...
So i understand the need for injection. Where to place the injections and how to size the wire to carry the load. The oart im still a little confused ...
Gotcha. So the only concern beyond that is the distance that 14/2 is running and the voltage drop. What kind of wire do you typically use for power i...
So increase the injection frequency or increase the injection wire size
It This is the pixel. Its rated for .6w so .05a. I agree. Id rather size for worst case scenario and play it safe. I can run a larger conductor if nec...
Ok so this is my proposed plan: Controller and power supply in the back left corner of the house. Left side is 212 pixels. First 100 fed from the co...
Thanks for the advice guys. Im leaning toward mounting the pixels on the outer part of the soffit facing out. I have a side street that runs perpendic...
Thanks. The hardest part to access is the sides of the house. The peak runs to the 2nd floor. Its accessible w/ a ladder. For the install, I may ren...
I definitely want it to last. Main reason lm doing it is im tired of putting lights on the roofline every Christmas. Im having the siding but not the ...